Programming, The microcomputer control center, Programming system setpoints – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 14: Fig. 5 – keypad – programming systemsetpoints

Advertising
background image

14

YORK INTERNATIONAL

PROGRAMMING

THE MICROCOMPUTER CONTROL CENTER

FIG. 5 – KEYPAD – PROGRAMMING SYSTEM

SETPOINTS

PROGRAMMING SYSTEM SETPOINTS

The system setpoints can be entered at any time . . . . .
even when the system is running. Proceed as follows to
enter system setpoints. (Refer to Fig. 5.)

1. Press ACCESS CODE key.

2.

ENTER VALID ACCESS CODE _ _ _ _

is displayed.

3. Using ENTRY keys, enter 9 6 7 5.

4. As each digit is entered, the characters Y O R K are

displayed.

NOTE: If digits other than 9 6 7 5 are entered,

Y O R K is still displayed.

NOTE: For ease in remembering the code, note that

the letters Y O R K correspond to the dig-
its 9 6 7 5 on a telephone dial

.

5. Press ENTER key.

NOTE: If digits other than 9 6 7 5 were entered in step

No. 4,

INVALID ACCESS CODE

is displayed

when the ENTER key is pressed. If this oc-
curs, enter the correct access code (9675)
and proceed.

6.

ACCESS TO PROGRAM KEY AUTHORIZED

is displayed.

NOTE: Unless terminated by pressing the ACCESS

CODE key again, the operator will have ac-
cess to the PROGRAM key for 10 minutes.
When 10 minutes have elapsed, access to
PROGRAM key will be automatically disabled
and the operator must return to step No. 1 to
gain access.

7. Press PROGRAM key.

8.

PROGRAM MODE, SELECT SETPOINT

is displayed.

9. Enter setpoints as detailed below. If you make a mis-

take when entering a value, press CANCEL key and
then ENTER key. The display will revert to the default
values and the cursor will return to the first change-
able digit. You can then proceed to enter the correct
values. If the entered value exceeds acceptable lim-
its,

OUT OF RANGE – TRY AGAIN!

message will be displayed for 2 seconds, then the

PROGRAM MODE, SELECT SETPOINT

message will re-

appear.

10. When all the desired setpoints have been entered,

press the ACCESS CODE key to exit PROGRAM
mode and terminate access to PROGRAM mode.

ACCESS TO PROGRAM MODE DISABLED

is displayed.

The Control Center will automatically return to LO-
CAL
, REMOTE or SERVICE mode . . . . whichever
was last selected.

LD00954

Advertising
This manual is related to the following products: