Detail a – compressor prerotation vanes, Capacity control, Fig. 2 – refrigerant flow-thru chiller – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 5

Advertising
background image

YORK INTERNATIONAL

5

FORM 160.49-O2

7619A(D)

DETAIL A – COMPRESSOR PREROTATION VANES

design conditions. However, most systems will be called
upon to deliver full load capacity for only a relatively
small part of the time the unit is in operation.

CAPACITY CONTROL

The major components of a chiller are selected for full
load capacities, therefore capacity must be controlled to
maintain a constant chilled liquid temperature leaving
the cooler. Prerotation vanes (PRV), located at the en-
trance to the compressor impeller, compensate for varia-
tion in load (See Fig. 2. Detail A).

The position of these vanes is automatically controlled
through a lever arm attached to an electric motor lo-
cated outside the compressor housing. The automatic
adjustment of the vane position in effect provides the
performance of many different compressors to match
various load conditions from full load with vanes wide
open to minimum load with vanes completely closed.

FIG. 2 – REFRIGERANT FLOW-THRU CHILLER

PREROTATION VANES
(See Detail A)

SUCTION

COOLER

ELIMINATOR

OIL COOLER

LD00924

FLOW CONTROL
ORIFICE

SUB-COOLER

CONDENSER

DISCHARGE
BAFFLE

DISCHARGE

COMPRESSOR

Advertising