York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 46

Advertising
background image

46

Y

ORK INTERNA

TIONAL

TABLE 1 – CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL,

CENTER DISPLAY

SHUTDOWN CAUSE

GOVERNING CONTROL FUNCTION

CONTROL CENTER DISPLAY

OPERATING

PROGRAMMED

START-UP OF

PROBABLE CAUSE

DAY OF

TIME OF

CAUSE OF

METHOD OF

DESCRIPTION

POINT

SETPOINTS

SYSTEM AFTER

AND SERVICE

WEEK

DAY

SHUTDOWN

RESTART

ON

ON

BY OPERATOR

SHUTDOWN

REQUIRED

RISE

FALL

MON.

10:00 AM

Oil Pressure

High Oil Press.

100 PSID (Dur-

59

Will start at 59

This Shutdown is provided

Transducer

Transducer

ing first 7 min. of

PSID

PSID when compr.

to check on Oil Pressure

Error

Compr. Oper.)

switch is placed to

Transducers for failure in

60 PSID (After

STOP/RESET and

the high state. Replace

first 7 min. of

then START

Oil Press. Transducer in

Compr. Oper.)

oil sump or compressor

Vane Motor

Autostart

Vane Motor

Restart automatically

Vanes are set improperly,

Switch Open

Switch

after Vane Motor arm

reset vane linkage check

linkage is set pro-

vane positions using

perly. Press STOP/

the SERVICE key switch

RESET and then

and proper keys on the

START switch

MicroComputer Control
Center

MON.

10:00 AM

Starter

Motor Current >

Press compressor

Check motor starter

Malfunction

15% for 10 swc.

STOP/RESET

operation. Motor current

Detected

with Control Cen-

switch and then

value greater than 15%

ter not calling for

FLA

motor to run

MON.

10:00 AM

Program

Autostart

Micro Board

Watchdog timer circuit

Initiated

has reset software pro-

Reset

gram – Chiller will
automatically restart.

Replace RTC

RTC-IC chip

Reprogram the Con-

Weak battery

IC chip

trol Center Setponts

Replace RTC-IC chip

Reprogram

& proceed with

U16

Setpoints

Normal Start-up

MON.

10:00 AM

Low Oil

Autostart

Oil Temp.

71.0°F

55°F

Press STOP/

Oil Temp. Thermistor

Temperature

Thermistor

RESET switch &

disconnected from

(RT3)

then START

Analog Input Board.

switch

Reconnect or replace
open sensor.

MON.

10:00 AM

Faulty Dis-

Discharge Temp. 30.0°F

29.9°F

Press STOP/

Faulty Discharge Temp.

charge Temp.

Thermistor

START switch &

Thermistor (RT2) or dis-

Sensor

(RT2) discon-

then START

connected from Analog

nected or faulty

switch

Input Board. Connect or

operating temp.

replace open sensor.

= 32°F

MON.

100.00 AM

Low Line

SSS Logic

See legend on wiring

Chiller will automa-

Low AC Line Voltage

Voltage (SSS

Board

diagram

tically restart when

Units only)

all phases of line vol-
tage increase to the
minimum required
starting level.

MON.

10:00 AM

MTR Phase

SSS Logic

See “Section 2”

Press STOP/START

Motor Phase Current

Current

Board

switch then START

Unbalance

unbalance

switch

(SSS Units
only)