York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 45

Advertising
background image

Y

ORK INTERNA

TIONAL

45

FORM 160.49-O2

MON.

10:00 AM

Low Evap.

Low Evap.

54.3

54.4

To restart, press

See OPERATION

Pressure

Pressure

PSIG (R-22)

PSIG (R-22)

compressor switch

ANALYSIS Table 2

Transducer

25

25.1

from STOP/RESET

Symptom 2

(LEP)

PSIG (R-134a)

PSIG (R-134a)

to START position

MON.

10:00 AM

Low Evap.

LEP external

Set to Job

Set to Job

To restart, press

See OPERATION

Pressure

control (Brine

Spec.

Spec.

compressor switch

ANALYSIS Table 2

Brine

units only)

from STOP/RESET

Symptom 2.

to START position

MON.

10:00 AM

Low Oil

Low Oil

25

15

Will restart when

Refer to OPERATION

Pressure

Pressure

PSID

PSID

pressure increases

ANALYSIS Table 2

Transducer

to 25 PSID. To

Symptoms 4, 5, 6, 7,

(OP)

restart, press com-

9, 10, 11

pressor switch from
STOP/RESTART to
START position.

MON.

10:00 AM

High

High Pressure

265

205

Will restart when

See Operational

Pressure

Safety Control

PSIG (R-22)

PSIG (R-22)

Pressure falls to

Analysis Table 2

(HP)

180

120

205 PSIG. To restart

Symptom 1 High

PSIG (R-134a)

PSIG (R-134a)

press compressor

Discharge Pressure

switch from STOP/
RESET to START
position

MON.

10:00 AM

Evap. Trans.

Evap. Pressure

To restart press

Defective Evap. Pressure

or Probe

Transducer or

compressor switch

Transducer or Leaving

Error

Leaving Chilled

from STOP/RESET

Chilled Water thermistor

Water Thermis-

to START position

(RS1). LCWT minus satu-

tor (RS1)

ration temperature is less
than –2.5°F or greater than
25°F. Checked every 10
minutes following a 10 min.
bypass at start-up.

MON.

10:00 AM

Motor Con-

CM2 or Solid

Reset the device

CM2, or Solid State

troller – Ext.

State Starter

that caused the shut-

Starter has shutdown

Reset

(RT2)

down. Chiller will

chiller

start automatically.

MON.

10:00 AM

High

Discharge Temp.

220°F

219°F

To restart press

Condenser tubes dirty or

Discharge

Thermistor

compressor switch

scaled or high condenser

Temp.

(RT2)

from STOP/RESET

water temperature. (See

to START position.

Symptom 1, Table 1.)

MON.

10:00 AM

High Oil

Oil Temperature

170°F

169°F

To restart press

Dirty oil filter or restricted

Temp.

Thermistor

compressor switch

oil cooler line. Change oil

(RT3)

from STOP/RESET

filter. Refer to OPERATION

to START position

ANALYSIS Table 2,
Symptom 9.

MON.

10:00 AM

Power

Auto-Restart

Micro Board

8.29VDC

7.84VDC

Optional AUTO

Will restart automa-

Power Failure.

Failure

undervoltage

Restart Plug is

tically when voltage

circuit on 5V

installed on

reaches 8.29VDC.

unregulated

Micro Board

An undervoltage

supply

circuit on the Micro
Board monitors the
5VC unregulated
supply for an under-
voltage condition.

MON.

10:00 AM

Power

Micro Board

8.29VDC

7.84VDC

Auto restart plug

To restart, press

Power Failure

Failure

undervoltage

is removed on

compressor switch

circuit on 5V

Micro Board

to STOP-RESET

unregulated

Position and then to

supply

START position

(Continued on page 46)