York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 23

Advertising
background image

YORK INTERNATIONAL

23

FORM 160.49-O2

Therefore:

(100%) (50% x 200) = 100A = Vanes stop open-
ing

(104%) (50% x 200) = 104A = Vanes driven to-
ward close position.

SYSTEM RUN – AUTO VANES

Displayed when the chiller is running, the MicroCom-
puter Control Center is in SERVICE mode, and the
vanes are operating in AUTO mode.

SYSTEM RUN – VANES OPENING

Displayed when the chiller is running, the MicroCom-
puter Control Center is in SERVICE mode with:

• The vanes operating in AUTO mode and opening to

maintain the leaving chilled water temperature
setpoint.

– or –

• The operator has pressed the vanes OPEN key on

the keypad.

SYSTEM RUN – VANES CLOSING

Displayed when the chiller is running, the MicroCom-
puter Control Center is in SERVICE mode with:

• The vanes operating in AUTO mode and closing to

maintain the leaving chilled water temperature
setpoint.

– or –

• The operator has pressed the vanes CLOSE key on

the keypad.

SYSTEM RUN - VANES HOLDING

Displayed when the chiller is running, the MicroCom-
puter Control Center is in SERVICE mode, and the
operator has pressed the vanes HOLD key.

SYS READY TO START – VANES OPENING

Displayed when the chiller is running and the operator
has pressed the vanes OPEN key on the keypad.

SYS READY TO START – VANES CLOSING

Displayed when the chiller is not running and the op-
erator has pressed the vanes CLOSE key on the key-
pad.

SYS READY TO START – VANES HOLDING

Displayed when the chiller is running and the operator
has pressed the vanes HOLD key on the keypad.

SYSTEM RUN – LEVEL VALVE OPENING

Displayed as a foreground message when manual re-
frigerant level control has been selected using the “Spe-
cial Setpoints Procedure” in Service manual, Form
160.49-M3 and operating in SERVICE mode. Indicates
an “OPEN” command is being output to the variable
orifice. Manual level control should be selected only by
a qualified service technician.

SYSTEM RUN – LEVEL VALVE CLOSING

Displayed as a foreground message when manual re-
frigerant level control has been selected using the “Spe-
cial Setpoints Procedure” in Service manual, Form
160.49-M3 and operating in SERVICE mode. Indicates
a “CLOSE” command is being output to the variable
orifice. Manual level control should be selected only by
a qualified service technician.

SYSTEM RUN – AUTO LEVEL CONTROL

Displayed as a foreground message when manual re-
frigerant level control has been selected using the “Spe-
cial Setpoints Procedure” in Service manual, Form
160.49-M3 and operating in SERVICE mode. Indicates
that neither a “CLOSE” nor “OPEN” command is being
output to the variable orifice but is in “AUTO” mode.
Manual level control should be selected only by a quali-
fied service technician.

SYSTEM RUN – LOW PRESSURE LIMIT IN EFFECT

Displayed when the chiller is running and the evapora-
tor pressure falls to 56.2 PSIG (R-22); 27 PSIG (R-
134a). Simultaneously, the pre-rotation vanes will be
prevented from further opening. This action maintains
chiller operation to prevent low-evaporator-pressure
shutdown at 54.3 PSIG (R-22); 25 PSIG (R-134a).
When the evaporator pressure rises to 57.5 PSIG (R-
22); 28 PSIG (R-134a), the vanes will be permitted to
open. Low pressure limit feature is not used when pro-
gram jumper (JP3) is cut (Brine application).

SYSTEM RUN – HIGH PRESSURE LIMIT IN EFFECT

Displayed when the chiller is running and the condenser
pressure rises to 246.3 PSIG (R-22); 162.5 PSIG (R-
134a). Simultaneously, the pre-rotation vanes will be
inhibited from further opening. This action occurs to
prevent system shutdown on high condenser pressure