Handling refrigerant for, Megging the motor, Fig. 23 – diagram, megging motor windings – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 53

Advertising
background image

YORK INTERNATIONAL

53

FORM 160.49-O2

HANDLING REFRIGERANT FOR

DISMANTLING AND REPAIRS

MEGGING THE MOTOR

If it becomes necessary to open any part of the refriger-
ant system for repairs, it will be necessary to remove the
charge before opening any part of the unit.

While the main disconnect switch and compressor
motor starter are open, meg the motor as follows:

1. Using a megohm meter (megger), meg between

phases and each phase to ground (see Fig. 23);
these readings are to be interpreted using the graph
shown in Fig. 24.

2. If readings fall below shaded area, remove external

leads from motor and repeat test.

NOTE: Motor is to be megged with the starter at

ambient temperature after 24 hours of idle
standby.

FIG. 23 – DIAGRAM, MEGGING MOTOR WINDINGS

LD00475