Section 5, Operational maintenance, Oil return system – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 42: Fig. 19 – oil return system

Advertising
background image

42

YORK INTERNATIONAL

SECTION 5

OPERATIONAL MAINTENANCE

OIL RETURN SYSTEM

The oil return system continuously maintains the proper
oil level in the compressor oil sump. (See Figs. 18 &
19.)

High pressure condenser gas flows continuously
through the eductor inducing the low pressure, oil rich
liquid to flow from the evaporator, through the dehydra-
tor to the compressor sump.

CHANGING THE DEHYDRATOR

To change the dehydrator, use the following procedure:

1. Shut the stop valves on the condenser gas line, oil

return line to rotor support and inlet end of the de-
hydrator.

2. Remove the dehydrator. Refer to Fig. 19.

3. Assemble the new filter-drier.

4. Open condenser stop valve and check dehydrator

connections for refrigerant leaks.

5. Open all the dehydrator stop valves to allow the

liquid refrigerant to flow through the dehydrator and
condenser-gas through the eductor.