SECTION 6

T

R

OUBLESHOO

TING

TABLE 1 – CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER CONTROL,

CENTER DISPLAY

SHUTDOWN CAUSE

GOVERNING CONTROL FUNCTION

CONTROL CENTER DISPLAY

OPERATING

PROGRAMMED

START-UP OF

PROBABLE CAUSE

DAY OF

TIME OF

CAUSE OF

METHOD OF

DESCRIPTION

POINT

SETPOINTS

SYSTEM AFTER

AND SERVICE

WEEK

DAY

SHUTDOWN

RESTART

ON

ON

BY OPERATOR

SHUTDOWN

REQUIRED

RISE

FALL

MON.

10:00 AM

Low Water

Autostart

Low Water

Chilled

4°F below

4°F below chilled

Automatic Restart

System load is less

Temp.

(LWT)

water

chiller

water setpoint

when water reaches

than minimum

setpoint

water

(If set to 40°F

setpoint; if system

capacity

setpoint

would be 36°F)

is running and set-

(36°F minimum

point is increased

4°F, system will
continue to run, as
LWT cutout shifts
to a fixed 36°F for
10 minutes.

MON.

10:00 AM

Flow Switch

Autostart

Flow Switch

Automatic Restart

Lack of water flow.

when water flow is

Check operation of

Restored to close

chilled water pump

flow switch.

MON.

10:00 AM

System

Autostart

A remote com-

Automatic Restart

Contact-connected to

Cycling

mand (computer

upon remote

the Remote/Local

relay contact or

command.

cycling input of the

manual switch)

Digital input board

MON.

10:00 AM

Multi-Unit

Autostart

(Optional) Lead-

Automatic Restart

Contact-connected to

Lag Sequence

upon remote

the Multi-Unit cycling

Control

command.

input of the Digital
input board

MON.

10:00 AM

Internal

Autostart

Internal Clock

Daily Schedule

Will automatically

Pressing Compressor

Clock

Programmed to

restart when pro-

Start Switch over-

Shutdown Unit

grammed schedule

rides the program

permits

MON.

10:00 AM

AC under-

Autostart

<15% FLA for

Cycling shutdown oc-

voltage

25 continuous

curs when motor cur-

seconds

rent is >15% FLA for
25 seconds during
chiller operation

MON.

10:00 AM

Power Fault

Autostart

CM-2 Current

Will start automatic-

Motor Controller con-

Module or

tically following

tacts opening and

Solid State

coastdown

closing in less than 3

Starter

seconds due to a power
fault condition

Remote Stop

Energy manage-

Start up by start

Remote Stop Contact

ment System

signal from remote

Closure

start switch

MON.

Anti-Recycle,

Anti-Recycle

Will not start

Will restart when

Min. Time between

20 Min. Left

timer

until 30 Min.

time left = 00 Min.

successive compres-

timer is timed

sor starts is 30 min.