TABLE 2 – OPERATING ANALYSIS CHART

RESULTS

POSSIBLE CAUSE

REMEDY

1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURE

Temperature difference between liquid

Air in condenser.

refrigerant out and water off condenser
higher than normal.

High discharge pressure.

Condenser tubes dirty or .

Clean condenser tubes. Check water

scaled

conditioning.

High condenser water

Reduce condenser water inlet

temperature.

temperature. (Check cooling tower

and water circulation.)

Temperature difference between conden-

Insufficient condensing

Increase the quantity of water through

ser water on and water off higher than

water flow.

the condenser to proper value.

normal, with normal cooler pressure.

2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURE

Temperature difference between leaving

Insufficient charge of

Check for leaks and charge

chilled water and refrigerant in cooler

refrigerant.

refrigerant into system.

greater than normal with high discharge

Flow orifice blocked.

Remove obstruction.

temperature.

Temperature difference between leaving

Cooler tubes dirty or

Clean cooler tubes.

chilled water and refrigerant in the cooler

restricted.

greater than normal with normal discharge
temperature.

Temperature of chilled water too low with

Insufficient load for

Check prerotation vane motor opera-

with low motor amperes.

system capacity.

tion and setting of low water temper-
ature cutout.

3. SYMPTOM: HIGH COOLER PRESSURE

High chilled water temperature.

Prerotation vanes fail to

Check the prerotation vane motor

open.

positioning circuit.

System overload.

Be sure the vanes are wide open
(without overloading the motor) until
the load decreases.

4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHED

Low oil pressure displayed on control

Oil pump running in wrong

Check rotation of oil pump

center; compressor will not start.

direction.

(Electrical Connections).

Oil pump not running.

Check electrical connections to oil
pump and press manual reset on oil
pump starter mounted on condenser
shell.

5. SYMPTOM: COMPRESSOR STARTS, NORMAL OIL PRESSURE DEVELOPS, FLUCTUATES FOR
SHORT WHILE, THEN COMPRESSOR STOPS ON OIL PRESSURE CUTOUT

Oil pressure normal, fluctuates then

Unusual starting conditions

Drain the oil from the compressor and

compressor stops on Oil Pressure

exist, i.e., oil foaming in

charge new oil into the compressor.

Cutout. Display reading

resevoir and piping due to

(Refer to “Charging The System With

LOW OIL PRESSURE

.

lowered system pressure.

Oil”, page 39.)

Burned out oil heater.

Replace oil heater.