York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 15

Advertising
background image

YORK INTERNATIONAL

15

FORM 160.49-O2

To enter CHILLED LIQUID TEMP Setpoint: (Refer to
Fig. 6.)

1. Press and release CHILLED LIQUID TEMP setpoint

key. The following program prompt message will be
displayed:

LEAVING SETPOINT = XX.X °F (BASE)

(BASE) refers to the base or lowest setpoint avail-
able to an Energy Management System. If any En-
ergy Management System is applied, this value must
be entered into the Energy Management System.
Refer to previous explanation or REMOTE/RESET
TEMP RANGE,
page 11.

2. Use ENTRY keys to enter desired value.

3. Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

FIG. 6 – KEYPAD – PROGRAMMING “LEAVING

CHILLED WATER TEMP” SETPOINT

To Enter % CURRENT LIMIT Setpoint:
(Electro-Mechanical Starter, refer to Fig. 7)

1. Press and release % CURRENT LIMIT setpoint key.

The following program prompt message is displayed:

CURRENT LIMIT = XXX% FLA

2. Use ENTRY keys to enter desired value.

3. Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

(Solid State Starter, refer to Fig. 7)

1. Press and release % CURRENT LIMIT setpoint key.

The following program prompt message is displayed:

CURRENT LIMIT = XXX% FLA; MTR CUR = _ _ _ FLA

2. Use ENTRY keys to enter desired value.

NOTE: Motor Current FLA value is entered by YORK

factory and checked at system start-up. It
cannot be changed without special access
code. (Note to service technician: refer to
“Programming Instructions” in Service in-
struction, Form 160.49-M3.

3. Press and release ENTER key.

PROGRAM MODE, SELECT SETPOINT

message is displayed.

FIG. 7 – KEYPAD – PROGRAMMING “% CURRENT

LIMIT” SETPOINT

LD00955

LD00956

Advertising
This manual is related to the following products: