Service keys, Fig. 13 – keypad – service keys location – York Millennium YK M3 M3 G4 THRU YK S6 S4 J2 User Manual

Page 19

Advertising
background image

YORK INTERNATIONAL

19

FORM 160.49-O2

FIG. 13 – KEYPAD – SERVICE KEYS LOCATION

The Service keys are provided for the service techni-
cian’s use when performing routine maintenance or when
troubleshooting the system. The WARNING RESET and
PRE-ROTATION VANES keys are enabled in SERVICE
mode only. The remainder of the Service keys are en-
abled in SERVICE, LOCAL or REMOTE mode.

PRE-ROTATION VANES KEYS

If chiller is equipped with the REFRIGERANT LEVEL
CONTROL (and EPROM version C.02F(T).13 or later),
the pre-rotation vanes keys can be used to manually
control the refrigerant level variable orifice or the pre-
rotation vanes. The procedure to select either manual
vane or manual variable orifice control is contained in
“Special Setpoints and Programming Procedures” sec-
tion of Service manual, Form 160.49-M3 and must be
performed by a qualified service technician only.

OPEN – Press and release this key to drive the pre-
rotation vanes open. If the chiller is running,

SYSTEM RUN – VANES OPENING

is displayed. If chiller is

not running,

SYS READY TO START – VANES OPENING

is

displayed. The vanes will continue to open until the
CLOSE, HOLD, or AUTO (if temperature error requires
it) keys are pressed and released.

HOLD – Press and release this key to hold the pre-
rotation vanes in their present position. If the chiller is

running,

SYSTEM RUN – VANES HOLDING

is displayed.

If chiller is not running,

SYS READY TO START – VANES HOLDING

is displayed. The

vanes will remain stationary until the OPEN, HOLD, or
AUTO keys are pressed and released.

AUTO – Press and release this key to put the pre-rota-
tion vanes under LCWT control as long as the current
limit setpoint is not reached, which causes the current
limit function to override the LCWT control. If system is
running,

SYSTEM RUN – AUTO VANES

is displayed. The

actual opening and closing of the vanes is indicated on
the display. When the vanes are opening,

SYSTEM RUN – VANES OPENING

is displayed. If the vanes

are closing,

SYSTEM RUN – VANES CLOSING

is displayed.

Whenever the Control Center is in LOCAL, REMOTE or
PROGRAM mode, the vane control circuitry is automati-
cally placed in AUTO mode and the vanes operate to
control the leaving chilled water temperature to the pro-
grammed setpoint.

CLOSE – Press and release this key to drive the pre-
rotation vanes closed. If the chiller is running,

SYSTEM RUN – VANES CLOSING

is displayed. If chiller is

not running,

SYS READY TO START – VANES CLOSING

is

displayed. When the vanes are full closed,

SYS READY TO START – VANES CLOSED

is displayed. The

vanes will continue to close until the OPEN, HOLD, or
AUTO keys are pressed.

SERVICE KEYS

LD00963

Advertising
This manual is related to the following products: