VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 10
Technical Information
10
71 -1 … 75 - 1
Installation examples for liquid tanks
-
Select sensor type and installation in relation to
max. level to be measured.
-
Protect the inner side of the socket piece for
corrosion or use non-corrosive material.
-
In case of round tank ceilings, the sensor should
be installed on a socket piece not located in the
centre or on an opening (on half radius).
In closed vessels:
Tube or direct mounting. If socket
piece length 100 mm or for
VEGASON 71 / 73 or > 150 mm for
VEGASON 74 / 75 are required
(max. level) note the dimensions in
the following table.
In open vessels:
Mounting via
Mounting by means
access hatch:
of bracketry
Simple direct mounting
Max. socket piece length L at:
(dimensions in mm)
VEGASON
71 - 1
72 - 1
73 - 1
74 - 1
75 - 1
at socket
100
300
400
400
–––
–––
piece ø
150
300
500
400
300
300
200
–––
–––
500
400
400
250
–––
–––
600
500
500
300
–––
–––
–––
600
600
350
–––
–––
–––
700
700
Min. distance
300
500
800
800
1000
L
ø
45
°
Socket piece length