VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 34
Measurement, Current output
34
71 - 1 … 75 - 1
MODE 0 - 65 and 0 - 66
Output characteristic
for current output 1 and 2
The pulse-echo measuring system can be equipped
with a current module. The module has two current
outputs.
The characteristic of the current output is fixed by
an initial and final point.
The factory preset defines a course 4 … 20 mA
acc. to 0 … 100 %.
Within the total range of 0.00 … 20.00 mA each
current value can be programmed for a raising or
falling level.
The current-
∆
between initial and final value must
be min. 1 mA.
• select mode 0 - 65 in MODEFIELD
• program 16.00 mA in PARAMETER FIELD
• then store with STO-button
• select mode 0 - 66 in MODEFIELD
• program 00.00 mA in PARAMETER FIELD
• then store with STO-button
%
100
0
mA
20
4
End of characteristic
100 % ^ 16 mA
Start of characteristic
0 % ^ 0 mA
Factory preset
Programming example