VEGA VEGASON 71 - 1 … 75 - 1 User Manual
Page 40
Sensor optimization
40
71 - 1 … 75 - 1
Information for sensor optimization
If optimization is required, always compare the local
conditions with the programmed parameters - if
necessary correct or adapt.
Basic test of
Mode-no.
Information
Selection / measures
Page
1 - 09
product type
liquids or solids
p. 42
1 - 10
vessel geometry
vessel top flat or dished
p. 42
1 - 10
solid
define particle size /
p. 43
1 - 11
angle of repose
1 - 19
rate of level change
define in cm / sec.
p. 46
False echo tests
Mode-no.
Mode description
Page
False echo BEFORE useful echo (output too high)
1 - 07
start of working range
define
p. 41
1 - 14
…
17
false echo
learn (activate)
p. 45
1 - 18
profile interpolation
activate
p. 46
False echo AFTER useful echo (output too low)
1 - 08
end of working range
define
p. 41
1 - 12
/
13
multiple false echo
reduce
p. 44
1 - 21
/
22
max. gain
limited
p. 47
Supplementary programmings
1 - 23
measuring window
switch on or off
p. 48
1 - 24
false echo
determine
p. 48
1 - 25
real distance
program
p. 49
1 - 27
basic adjustment
define
p. 49