VEGA VEGASON 71 - 1 … 75 - 1 User Manual

Page 46

Advertising
background image

Adaption to filling and emptying speed

Rate of product level change

MODE 1 - 19

The rate of product level change is factory set by
VEGA within the adjustment range
-

0.01 … 11 cm / sec. with

-

4.00 cm / sec.

This adjustment should only be changed if this
seems useful in case the actual rate of product
level change exceeds the standard value.

Programming example
Change to 0,50 cm / sec. .........................................

• select mode 1 - 19 in MODEFIELD
• program 0.50 in PARAMETER FIELD
• then store with STO-button

Conversion schedule .............................................

cm / sec.

m / hours

Adjustment range ........

0,01

0,36

0,05

1,8

0,1

3,6

0,5

18,0

1,0

36,0

2,0

72,0

4,0

144,0

6,8

216,0

8,0

288,0

10,0

360,0

Storage of a false echo profile

46

71 - 1 … 75 - 1

Profile interpolation

MODE 1 - 18

With the function "false echo learn" gaps can exist
between the gated out false echoes.

With the activation of the profile interpolation, gaps,
smaller 3 m will be closed.

Build-up around struts, weldment joints etc. caused
after the time cycle, generate additional false
echoes.

Demonstration as comparison

Additional false echoes
by build-up

Programming example ..........................................

• select mode 1 - 18 in MODEFIELD
• program with figure 1 the profile interpolation in

PARAMETER FIELD

• then store with STO-button

Profile interpolation ..........................................

off ..............

on

Advertising