VEGA VEGASON 71 - 1 … 75 - 1 User Manual

Page 29

Advertising
background image

Measurement, Relay output

71 - 1 … 75 - 1

29

Mode

(Module 1, relay output 1) continuation

Mode 0 - 44 = 1
two-point level switch
switching command 1 via
switching command 2
corresponds to function B
(protection against dry
running of pumps)

Switching command 1 and 2

(Module 1, relay output 1)

MODE 0 - 45 and 0 - 46

Mode 0 - 43 defines the measurement units
coordinated to the relay output.

Mode 0-44 determines the function of the relay
output.

Mode 0-45 =

switching command 1 corresponds
to switch on (on)

Mode 0-46 =

switching command 2 corresponds
to switch off (off)

With the operating sequence of the switching
commands, the A- or B-function i.e. overfill protec-
tion or protection against dry running of pumps is
determined.
See diagram page 28 and 29.

The min.-

for the switching commands is 10 cm or

0,5 %.

Programming example for relay output 1 ...............

-

coordination to channel1 with units in %

-

mode 1

-

two-point level switch in function A
(see page 28)

Coordination ..............................................................

• select mode 0 - 43 in MODEFIELD
• program figure 2 in PARAMETER FIELD
• then store with STO-button

Mode (two-point level switch) ....................................

• select mode 0 - 44 in MODEFIELD
• program figure1 in PARAMETER FIELD
• then store with STO-button

Switching command 1 (on) ......................................

• select mode 0 - 45 in MODEFIELD
• program 025.0 % in PARAMETER FIELD
• then store with STO-button

Switching command 2 (off) .......................................

• select mode 0 - 46 in MODEFIELD
• program 050.0 % in PARAMETER FIELD
• then store with STO-button

Same function and procedure
for module 1, relay output 2
and module 2, relay output 3 and 4 however
with respective modes, see page 28.

0

25

75

100

50

% m

distance acc. to sensor type

switching command 1,
mode 0-45
switching command 2,
mode 0-46

(on)

(off)