Dished tank ceiling, Or 2“ thread to short socket pieces, Mounting and installation – VEGA VEGASCAN 850 User Manual

Page 40

Advertising
background image

40

VEGASCAN 850

Dished tank ceiling

On dished tank ceilings, please do not mount
the instrument in the centre, but approx.

1

/

2

vessel radius from the centre. Dished tank
ceilings can act as paraboloidal reflectors. If
the transducer is placed at the focal point of
the parabolic ceiling, the transducer receives
amplified false echoes. The transducer
should be mounted outside the focal point.
Amplified echoes caused by parabolic sur-
faces are thereby avoided.

It is also possible to mount the sensors with
1

1

/

2

“ or 2“ thread to short socket pieces.

Flange version and swivelling holder on flat vessel
top

Reference
plane

Reference
plane

< 60 mm

Mounting of the transducer with 1“ thread (here
belonging to VEGASON 54 version D)

Reference
plane

Min. meas. distance

1.8 m

Min. meas. distance

1.4 m

Swivelling
holder

VEGASON 54 … 56 sensors in version C are
mounted in a 1“ thread.

Mounting on short 1

1

/

2

“ or 2“ socket pieces (VE-

GASON 51)

Reference plane

£ 60 mm

Mounting and installation

VEGASON 51, 52 on dished tank ceiling

Reference plane

1

/

2

vessel radius

£ 60 mm