6 PC/DCS values

RS232/Ethernet connection • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30325-EN-130701

6 PC/DCS values

6.1 General information

PC/DCS outputs are used as digital outputs for transmission of meas-

ured value information. The data can be transmitted to a superordi-

nate PC, DCS or processing system via the RS232/Ethernet interface.

The values can be sent e.g. as e-mail or read out via Modbus TCP in

case of an existing Ethernet interface. The HTML pages of the signal

conditioning instrument also show the measured values of the PC/

DCS outputs. The adjustment of the data format and the reference

value is carried out with PACTware and the corresponding DTM. In

the parameter adjustment page "PC/DCS" the reference value and

the data format are selected; in addition, the option "In case of error:

transmit error code instead of measured value" can be activated.

With the reference value you determine which measured value is

used as input signal for the PC/DCS output. The following reference

values are available depending on the instrument:

Sensor value

Percent

Lin. percent

Scaled

Totalizer

With "Data format", the format of the PC/DCS value is determined.

Here you determine how many decimal positions will be transmitted.

This setting is important, e.g. with Modbus-TCP (filing of the meas-

ured value as 2 Byte short). The PC/DCS value is then transmitted in

the integer format, i.e. the value must be within the range of -32767

and +32767.
Example: The sensor value of a pressure transmitter should be

transmitted as PC/DCS value. The meauring range of the sensor is

between -0.5 bar and +0.5 bar, the value should be transmitted with

two positions after the decimal point. The following settings must

be carried out: The sensor value must be selected as "Basic meas.

value" and the selection #.## as "Data format". With these settings,

the sensor value -0.5 bar is transmitted as PC/DCS value -0.5 bar.

If " In case of error: send error code instead of measured value " is ac-

tivated, the number of the error code is sent instead of the measured

value. These numbers correspond to the numbers of the instrument

status.
Example: With error E008, value 8 is transmitted instead of the meas-

ured value.