VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 14

Advertising
background image

6 Plug the electronics housing to the transducer tube. Do not

squeeze any cables. The housing is in the correct position,

if the lower notch (2) of the transducer tube is no longer

visible

7 Tighten the screws (5) on the housing moderately with a

hexagon spanner (size 4)

8 Loosen terminal screw of the swivelling holder (3) with a

fork spanner (SW 13)

9 Direct the sensor with the swivelling holder to the

measured product

10 Fasten the swivelling holder with screw (3), torque max.

20 Nm

11 Secure screw (3) with lacquer or similar to ensure

permanent tightness of the swivelling holder

12 Rotate the housing in such a way that the cable entry

points downwards (moisture can drain off). Fasten the

housing with screws (5); torque Aluminium housing max.

5 Nm, torque plastic housing max. 2 Nm

14

VEGASON 66 - Foundation Fieldbus

Mounting

28795

-EN

-060731