VEGA VEGASON 66 Foundation Fieldbus User Manual
Page 14
6 Plug the electronics housing to the transducer tube. Do not
squeeze any cables. The housing is in the correct position,
if the lower notch (2) of the transducer tube is no longer
visible
7 Tighten the screws (5) on the housing moderately with a
hexagon spanner (size 4)
8 Loosen terminal screw of the swivelling holder (3) with a
fork spanner (SW 13)
9 Direct the sensor with the swivelling holder to the
measured product
10 Fasten the swivelling holder with screw (3), torque max.
20 Nm
11 Secure screw (3) with lacquer or similar to ensure
permanent tightness of the swivelling holder
12 Rotate the housing in such a way that the cable entry
points downwards (moisture can drain off). Fasten the
housing with screws (5); torque Aluminium housing max.
5 Nm, torque plastic housing max. 2 Nm
14
VEGASON 66 - Foundation Fieldbus
Mounting
28795
-EN
-060731