VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 35

Advertising
background image

Linearisation curve

linear

Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [->] key.
High sockets or vessel installations, such as e.g. struts or

agitators as well as buildup and weld joints on the vessel walls

cause interfering reflections which can impair the measure-

ment. A false echo storage detects and marks these false

echoes, so that they are no longer taken into account for the

level measurement. A false echo memory should be created

with empty vessel so that all potential interfering reflections will

be detected.

Gating out of false signals

Change now?

Proceed as follows:
1 Move from the measured value display to the main menu

by pushing [OK].

2 Select the menu item "Service" with [->] and confirm with

[OK]. Now the menu item "False signal suppression" is

displayed.

3 Confirm "False signal suppression - Change now" with

[OK] and select in the below menu "Create new". Enter the

actual distance from the sensor to the product surface. All

false signals in this area are detected by the sensor and

saved after confirming with [OK].

Note:

Check the distance to the product surface, because if an

incorrect (too large) value is entered, the existing level will be

saved as false signal. The filling level would then no longer be

detectable in this area.

Additional adjustment and diagnosis options such as e.g.

scaling, simulation or trend curve presentation are shown in

the following menu schematic. You will find a detailed

description of these menu items in the operating instructions

manual of the indicating and adjustment module.

Gating out of false signals

Optional settings

Setup with the indicating and adjustment module PLICSCOM

VEGASON 66 - Foundation Fieldbus

35

28795

-EN

-060731