VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 33

Advertising
background image

3 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the

requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4 Enter the appropriate distance value in m (corresponding

to the percentage value) for the empty vessel (e.g. distance

from the sensor to the vessel bottom).

5 Save the settings with [OK] and move to "Max. adjustment"

with [->].

Proceed as follows:

Max. adjustment

100.00 %

=

1.000 m(d)

2.000 m(d)

1 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the

requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

2 Enter the appropriate distance value in m (corresponding

to the percentage value) for the full vessel. Keep in mind

that the max. level must lie below the dead band.

3 Save the settings with [OK] and move to "Medium

selection" with [->].

Each product has different reflective properties. In addition,

there are various interfering factors which have to be taken into

account: agitated product surfaces and foam generation (with

liquids); dust generation, material cones and echoes from the

vessel wall (with solids). To adapt the sensor to these different

conditions, you should first select in this menu item "Liquid" or

"Solid".

Medium

Liquid

With solids, you can also choose between "Powder/Dust",

"Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted

perfectly to the product and measurement reliability, partic-

ularly in products with bad reflective properties, is considerably

increased.

Carry out max. adjustment

Medium selection

Setup with the indicating and adjustment module PLICSCOM

VEGASON 66 - Foundation Fieldbus

33

28795

-EN

-060731

Advertising