VEGA VEGASON 66 Foundation Fieldbus User Manual

Page 45

Advertising
background image

-

Channel 3

Secondary Value 2

-

Channel 4

Temperature value

Transmission rate

31.25 Kbit/s

Current value

10 mA; ±0.5 mA

Input variable
Parameter

-

Version A

distance between lower edge of the flange and

product surface

-

version B, C and D

distance between lower edge of the transducer

and product surface

Dead zone

-

Version A

1.8 m (5.9 ft)

-

Versions B, C, D

1.4 m (4.6 ft)

Measuring range

-

Liquids

up to 70 m (229.7 ft)

-

Solids

up to 45 m (147.6 ft)

Accuracy (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

-

Temperature

+18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa

(12.5 … 15.4 psi)

Deviation in characteristics and characteristics

4)

Average temperature coefficient of the

zero signal (temperature error elec-

tronics)

0.06 %/10 K

Resolution, general

max. 1 mm

Ultrasonic frequency

10 kHz

Interval

>2 s (dependent on the parameter adjustment)

Beam angle at -3 dB

4)

Relating to the nominal range, incl. hysteresis and repeatability, determined

according to the limit point method.

Supplement

VEGASON 66 - Foundation Fieldbus

45

28795

-EN

-060731

Advertising