3 operation – VEGA VEGAFLEX 66 (-110…+400°C) 4 … 20 mA_HART User Manual

Page 10

Advertising
background image

I

t is designed for industrial use in all areas of process

technology and can be used in non-conductive liquids.

H

igh frequency microwave pulses are guided along a steel

rope or a rod. Upon reaching the product surface, the
microwave pulses are reflected. The running time is evaluated
by the instrument and outputted as distance.

T

wo-wire electronics 4 … 20 mA/HART for power supply and

measured value transmission over the same cable.

T

he supply voltage range can differ depending on the

instrument version.

D

ata for power supply are specified in chapter "Technical

data".

T

he backlight of the indicating and adjustment module is

powered by the sensor. The prerequisite for this is a supply
voltage at a certain level. The exact voltage specifications are
stated in chapter "Technical data".

T

he optional heating requires its own power supply. You can

nd further details in the supplementary instructions manual

"H

eating for indicating and adjustment module".

T

his function is generally not available for approved instru-

ments.

3.3 Operation

VEGAFLEX

66

can be adjusted with different adjustment

media:

l

with indicating and adjustment module

l

with the suitable VEGA DTM in conjunction with an
adjustment software according to the FDT/DTM standard,
e.g. PACTware and PC

l

with manufacturer-specific adjustment programs AMS™ or
PDM

l

W

ith a HART handheld

T

he entered parameters are generally saved in VEGAFLEX

66,

optionally also in the indicating and adjustment module or

in PACTware.

Functional principle

Voltage supply

10

VEGAFLEX

66 • 4 … 20

mA/HART

3 P

roduct description

32762

-EN

-080716