Caution:
I

f there is a separation of different liquids in the vessel, e.g. by

condensation, VEGAFLEX 66 will always detect the medium
with the higher dielectric figure (ε

r

).

K

eep in mind that interfaces can cause faulty measurements.

I

f you want to measure the total height of both liquids reliably,

please contact our service department or use an instrument
specially designed for interface measurement.

S

tart your parameter adjustment with the following menu items

of the basic adjustment:

P

roceed as follows:

1 M

ove from the measured value display to the main menu

by pushing [OK].

B

asic adjustment

D

isplay

D

iagnostics

S

ervice

I

nfo

2 S

elect the menu item "Basic adjustment" with [->] and

confirm with [OK]. Now the menu item "Min. adjustment" is
displayed.

M

in. adjustment

0.00 %

=

10.000 m(d)

8.000

m(d)

3 P

repare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the
requested percentage value with [+] and save with [OK].
T

he cursor jumps now to the distance value.

4 E

nter the suitable distance value in m for the empty vessel

(

e.g. distance from the sensor to the vessel bottom)

corresponding to the percentage value.

5 S

ave the settings with [OK] and move to "Max. adjustment"

with [->].

P

roceed as follows:

M

ax. adjustment

100.00 %

=

1.000 m(d)

2.000

m(d)

Carrying out min. ad-
justment

Carrying out max. ad-
justment

VEGAFLEX

66 • 4 … 20

mA/HART

31

6 S

et up with the indicating and adjustment module PLICSCOM

32762

-

EN

-080716