VEGA VEGAFLEX 66 (-110…+400°C) 4 … 20 mA_HART User Manual

Page 43

Advertising
background image

?

4 … 20

mA signal missing

l

W

rong connection

à Check connection according to chapter "Connection

steps" and if necessary, correct according to chapter
"W

iring plan"

l

N

o voltage supply

à Check cables for breaks; repair if necessary

l

supply voltage too low or load resistance too high

à Check, adapt if necessary

?

C

urrent signal greater than 22 mA or less than 3.6 mA

l

E

lectronics module defective

à Exchange instrument or return instrument for repair

I

n Ex applications, the regulations for the wiring of intrinsically

safe circuits must be observed.

?

E

013

l

no measured value available

à sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty

installation or wrong parameter adjustment

à Wrong sensor length entered

?

E

017

l

A

djustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send the instrument for

repair

?

E

042/E043

l

H

ardware error, electronics defective

à Exchange instrument or return instrument for repair

Fault messages via the
indicating/adjustment
module

VEGAFLEX

66 • 4 … 20

mA/HART

43

8 M

aintenance and fault rectification

32762

-

EN

-080716

Advertising