6 L

ift the opening levers of the terminals with a screwdriver

(

see following illustration)

7 I

nsert the wire ends into the open terminals according to

the wiring plan

Fig. 7: Connection steps 6 and 7

8 P

ress down the opening levers of the terminals, you will

hear the terminal spring closing

9 C

heck the hold of the wires in the terminals by lightly

pulling on them

10 C

onnect the screen to the internal ground terminal, connect

the outer ground terminal with potential equalisation

11 T

ighten the compression nut of the cable entry. The seal

ring must completely encircle the cable

12 S

crew the housing cover on

T

he electrical connection is finished.

5.3 Wiring plan, single chamber housing

T

he following illustrations apply to the non-Ex as well as to the

E

x-ia version.

20

VEGAFLEX

66 • 4 … 20

mA/HART

5 C

onnecting to power supply

32762

-EN

-080716