1 INSTALLATION

1.9 Cubicles

Inverter is delivered with external braking resistor. Braking resistor types D2FR are installed in the same cubicle as the
inverter itself. Braking resistor D2HR04F90R0S4 for 002 –005 is in own cubicle.

Power class

Standard cubicle

Cubicle size (mm)

Braking resistor (mm)

002 - 005

EEO25.604

400 x 600

400 x 400

007 – 015

CC600E

600 x 1000

Included

018 – 030

KA220D2

1000 x 1000

Included

037, 045

1½ x KA220D2

1½ x 1000 x 1000

Included

055

1½ x H15BD02

1½ x 1500 x 1000

Included

1.10 Braking resistor

Inverter is delivered with external braking resistor. Braking resistor types D2FR are equipped with cooling fans and
thermistors. Circuit diagrams are in appendix.

Power class

Resistance (ohm)

Type

002 - 005

90

D2HR04F90R0S4

007

64

D2FR06F64R0S2

011, 015

45

D2FR12F45R2S2

018, 022

21

D2FR18F21R3S2

030

16

D2FR24F16R4S2

037, 045

11

2 x D2RF18F21R3S2

055

8

2 x D2FR24F16R4S2

In case of 2 resistor units, power supply to transformers has to be taken from the same phases.

1.11 Power cabling

1.11.1 Shielded motor cable

In crane application inverter fulfils EN61800-3/A11 (IEC 1800-3) second environment radiated emission requirements
without shielded motor cable.

In the second environment, shielded motor cable is recommended to use in fixed installations, especially in buildings.
However motor cables in crane and festoon power supplies are normally not shielded due to the practical reasons.

1.11.2 Double collectors

If the power is supplied to the crane via conductor rails, double collectors are needed. This ensures a reliable contact with
the rail in all circumstances. Short interruptions and sparks between the conductor rail and the collector may cause
nuisance tripping, other undesired operations and in worst case even permanent damage to components.

1.11.3 Cable selection

Cabling for inverter can be done using normal crane cables. All the cables must be dimensioned according to local
regulations. Ambient temperature, cabling method (size of bunches etc.) and allowable current for the cable in use must
be taken into consideration. If there are no other regulations, following values can be used (three phase 400V supply).

The table below is based on ED

60% and ambient temperature +40°C (104°F). A highe r ambient temperature may

require increased cable sizes. The input current does not exceed the continuous current (Icont) of inverter, so it is
selected to be the dimensioning current. If the actual load current is below inverter continuous current, then the fuses and
the supply cable may be dimensioned according to the load current.