motor type plate parameters

maximum frequency parameters

F 70

Multicare Fault

Other inverter has tripped to fault or brake
of other inverter has not been opened.
Fault is not stored into fault history.

Check other hoisting inverter:

fault history

brake operation

X

F 71

Brake Control
Fault

Load information from hoist control unit is
out of operation window

Check

Ain2 wiring

settings of load measuring device

X

F 73

Both Dir Active

Both direction signals are active at same
time >500ms

Check

controller operation

wiring of direction signals

X

F 90

SystemBus fault

Communication error in SystemBus

Check

SystemBus wiring

SystemBus boards connections into the control units

Parameters P2.4.1, P2.4.2. and P2.4.3. in all drives

X

F 91

SystemBus Brake
supervision

All units are not giving brake opening or
closing information during 500ms.

Check

That each active drive gets direction signals (S1/S2).

That ramp times are similar in each drive

X

F 92

Synchronization
Displacement

Displacement limit has been exceeded.
Difference in acceleration, deceleration or
braking times between the drives.

Check

That ramp times are similar in each drive

Value of parameter P2.4.5. “Displacement Lim” in
master drive

Speed feedback operation

Mechanical brake operation and adjustments

X

F 93

SystemBus
Activation

Synchro activation is not done in correct
operation state.

Stop driving before the Synchro is activated or
deactivated

X

A = Can be done by the user

B = Can be done only by manufacturer authorized personnel

3.3.1 Fault time data record


When a fault occurs, the fault number is displayed. By pushing the menu button right here you will enter the Fault time
data record menu, indicated by T.1-T.13.

In this menu, some selected important data valid at the time of the fault are recorded. The data available are:

T.1

Counted operation days

d

T.2

Counted operation hours

hh:mm:ss

T.3

Output frequency

Hz

T.4

Motor current

A

T.5

Motor voltage

V

T.6

Motor power

%

T.7

Motor torque

%

T.8

DC voltage

V

T.9

Unit temperature

°

C

T.10

Ready

Run

0=Not Ready

1=Ready

0=Not Running

1=Run

T.11

Direction

Fault

0=Off

1=On

0=No

1=Yes

T.12

Warning

At reference

0=No

1=Yes

0=No

1=Yes

T.13

0-speed

0=Not Zero Speed

1=Zero Speed