Figure 3-7 Connection of Digital Input Port

3.5.3 ADC Input Port

An ADC input port is a non-insulated input port. If possible, a circuit should be made using

AVCC (+5V) voltage supplied from internal circuits. When operating in Switch mode, a threshold

voltage should be specified. Input is set to ON and the ADC status LED is ON if the input

voltage is higher than the specified threshold value. Conversely, input is set to OFF and the LED

turns off when the input voltage is lower than the threshold. The ADC status LED operates only

when it is set as Switch mode.

1) Connecting reference voltage (AREF) in analog input

AREF can be set as either internal 2.56 V, internal AVCC or external AREF point. Internal input

can be set using command. The external input can be set by splitting the AVCC voltage into R1

and R2 as shown below. The ideal resistance of split resistors R1 and R2 should be within the

range of 1㏀ - 5㏀.

Note) AREF voltage cannot be set to the value less than 2 V.

Figure 3-8 Connecting Aref