Setting references from isbus to drive, Isbus pages – GE Industrial Solutions Control System Toolbox For an AV-300i Version 2 Drive User Manual

Page 63

Advertising
background image

GEH-6412 Toolbox for AV-300i Version 2 Drive

Chapter 4 Configuring an AV-300i Version 2 Drive

••••

4-33

ISBus Pages

Pages provide a way to share live signals over the ISBus. Pages are defined in the
drive and their definition is published to the controller through the SDB. The drive
has a set of pages with a default signal layout and define commonly used signals.
The individual pages can be customized to change the signals, which are exchanged
between the drive and the controller. For the AVDV drive, the maximum size of a
page is 16 bytes, organized as eight 16-bit words. Booleans are transferred as single
bits. They are defined using a bit number word number notation, where the word
number ranges from 1–7, and the bit number ranges from 0–15.

Setting References from ISBus to Drive

Ø To set a reference to be controlled from the ISBus

Refer to the section, Using the
Finder.

Or click the right mouse
button and select Modify.

Refer to the section, Editing
Parameters.

1. Using the Finder, locate the parameter that you want controlled from the ISBus

(for example, Ramp ref 1 src). Then click the Goto button to display the
parameter location in the Outline View.

2. Click on the parameter name. From the Edit menu, select Modify. The Edit

Parameter dialog box displays.

3. From the Value drop-down list, select the appropriate value for the ISBus

interface (using the example above, ISBus Drv W1 mon). The Ramp Ref 1 src
is controlled from the ISBus.

Advertising