CPS2500D +/-190V Downstream System
2 - 2 Product Description
Issue 4 January 2008
Operation
Power comes in on P800 from up to 20 independent 100VA +/- 190V circuits.
Power comes out on P700 at -54 volts. Maximum current for a fully
provisioned shelf is 24 Amps or 1300 Watts. Major and minor alarms are
available on P321. The alarms are configured as Form C closures. A major
indicates circuit or input failure on 2 or more circuits. A minor alarm indicates
circuit or input failure of one circuit.
Section 5 has a step by step installation and trouble shooting process using the
Display LEDs as a primary guide to next actions.