Installing the converters, Qs882a converter installation, Install the qs882a converters – GE Industrial Solutions CPS2500D +-190V User Manual

Page 35: Figure 5-5: align the qs882a converter, Figure 5-6: qs800a with all cables attached

Advertising
background image

CPS2500D +/-190V Downstream System

Issue 4 January 2008

Installation 5 - 7

Installing the Converters

QS882A Converter
Installation

QS882A Converters mount in the QS800 shelf. Note that numbering starts
from the left and is correlated to the marking on the 5-pin protector block
cabinet input wiring panels.

Warning: You must properly protect yourself against ESD discharge prior
to installing the QS882A Controller.

Note: There is an ESD cord connection located on the right side of the shelf.

Install the QS882A
Converters

This procedure is used to install each QS882A Converter.

Step

Action

1

Remove the QS882A converter from its shipping container.

2

Align the plastic converter housing on the right and insulated
circuit board on the left.

3

Guide the converter into the first available slot by positioning the
plastic converter housing in the notch on the top right edge of the
opening. See Figure 5-5.

4

Slide the converter into the shelf until it is fully seated in the
connector on the rear of the CPS shelf.

5

Push the display faceplate into the shelf until the latch on the top of
the converter housing catches. See Figure 5-6.

6

Repeat this process as needed for your application.

Figure 5-5: Align the QS882A Converter

QS882A

A

B

IN

OUT

Push in until
latch clicks

Figure 5-6: QS800A with All Cables Attached