CPS2500D +/-190V Downstream System

Issue 4 January 2008

Electrical Interface Reference Information 6 - 3

P321

P321

Pin

Function

1

Power Major Alarm NC

2

Power Major Alarm Common

3

Power Major Alarm NO

4

Power Minor Alarm NC

5

Power Minor Alarm Common

6

Power Minor Alarm NO

7-16

No Connection

Notes:Both alarms are fail-safe isolated Form C contact closures

NC = Normally Closed, NO = Normally Open
Use same ratings for relays as CPS4000 alarm relays

Alternate Alarm Wireset

Alarm Output Connector

Pin

Function

1

Power Major Alarm NC

2

Power Major Alarm Common

3

Power Major Alarm NO

4

Power Minor Alarm NC

5

Power Minor Alarm Common

6

Power Minor Alarm NO

Notes:Both alarms are fail-safe isolated Form C contact closures

NC = Normally Closed, NO = Normally Open
Use same ratings for relays as CPS4000 alarm relays

To create a custom wireset that connects directly to the shelf, mate for the
Alarm Output Connector can be constructed using:

• AMP 6 Position Housing 1445022-6

• AMP Socket Contact 794606-1

• 22 AWG Stranded Wire