Engineering, Engineering 3-2, Figure 3-1: constant delivered power curves – GE Industrial Solutions CPS2500D +-190V User Manual

Page 20: Normal range of operation)

Advertising
background image

CPS2500D +/-190V Downstream System

3 - 2 Engineering and Ordering

Issue 4 January 2008

Engineering

Engineering a telephone line powered system requires knowledge about the
resistance of the input wires feeding each circuit. To make a rough estimate
follow these steps. An example follows each step in [ ] brackets.

1. Assess the total resistance of the loop feeding each circuit. [ 600

Ω ]

2. Decide how much power your load requires. [ 600W ]

3. Choose the highest power curve available for circuits with the input

resistance provided by your network. [ For 600

Ω, the 60Watt line almost

works. This looks like about 58 Watts.]

Figure 3-1: Constant Delivered Power Curves

(normal range of operation)