Electrical, Electrical 2-4, Table 2-b: electrical specifications – GE Industrial Solutions CPS2500D +-190V User Manual

Page 16

Advertising
background image

CPS2500D +/-190V Downstream System

2 - 4 Product Description

Issue 4 January 2008

Electrical

Unless otherwise specified, specifications apply over all operating input
voltage, output load current and temperature conditions.

Table 2-B: Electrical Specifications

Parameter

Symbol

Min

Typ

Max

Unit

Input
Operating Input Voltage

Vi

130

391.1

400

Vdc

Maximum Input Current

(±190 Vdc: Vioc=320 Vdc to 398 Vdc, Io=Io, max)

Future Code:

(±130 Vdc: Vioc=250 Vdc to 278 Vdc, Io=Io, max)

Iin max

0.233

0.314

0.241

0.33

0.250

0.347

Adc

Inrush Transient (Duration: <= 1.0 ms)

Ipk

0.25

Adc

Output (per Power Unit, 2 Circuits)
Output Voltage Set-point

(Vin=Vin min, Io=1.47A, Ta =25°C)

Vo, set

-54.5

Vdc

Output Voltage

(Over all operating input voltage, resistive load, and
temperature conditions until end of life)

Vo

-52.0

--

-55.0

Vdc

Output Regulation

Line (Vin=Vin min to Vin max)
Load* (Io=Io min to Io max)
*Output voltage droops as load current

increases to provide system current sharing.

Temperature (TA = -40°C to +85°C)

--
--

--

0.5

TBD

150

--

3.5

--

%Vo
%Vo

mV

Output Ripple and Noise on nominal output
(Vin=Vin nom and Io=Io min to Io max)

RMS (5Hz to 20MHz bandwidth)
Peak-to-Peak (5Hz to 20MHz bandwidth)

--
--

140
200

--
--

mVrms

mVpk

External Capacitance

Co max

--

--

3,000

µF

Output Power (per circuit pair, Vo=Vo min)

Io

0

2.5

Adc

Efficiency (Io=Io max, Vo=Vo set, Ta=25°C)

Vin=260V
Vin=380V

η

86
83

%

Dynamic Load Response
(

ΔIo/Δt=1A/10µs, Vin=Vin nom, Ta=25°C)

Load Change from Io=50% to 75% of Io max
Peak Deviation
Load Change from Io=75% to 50% of Io max
Peak Deviation
Settling Time (Vo<10% peak deviation)

Vpk

ts

Vpk

ts

%Vo set

µs

%Vo set

µs

Advertising