CPS2500D +/-190V Downstream System
Issue 4 January 2008
Product Description 2 - 3
Specifications
Table 2-A: Absolute Maximum Ratings
Parameter
Symbol
Min
Typ
Max
Unit
Input Voltage
Continuous
VI
0
380
400
Vdc
TransientDuration = 10ms
Vtr
400
TBD
Vdc
Temperature
Normal Operating Ambient
Temperature at 150 lfm airflow
TA
-40
65
°C
Operating Ambient Temperature at
higher (TBD) airflow
TA
-40
75
°C
(See Thermal Considerations section)
Storage Temperature
Tstg
-55
125
°C
Power
Input Power (per Power unit)
Pin
200
W
Power Dissipation (Power unit
Dissipation)
Pdiss
27
TBD
W
Output Power (per Power unit)
Pout
130
TBD
W
Isolation
Input to Output Voltage
1500
Vdc