Specifications, Specifications 2-3, Table 2-a: absolute maximum ratings – GE Industrial Solutions CPS2500D +-190V User Manual

Page 15

Advertising
background image

CPS2500D +/-190V Downstream System

Issue 4 January 2008

Product Description 2 - 3

Specifications

Table 2-A: Absolute Maximum Ratings

Parameter

Symbol

Min

Typ

Max

Unit

Input Voltage
Continuous

VI

0

380

400

Vdc

TransientDuration = 10ms

Vtr

400

TBD

Vdc

Temperature
Normal Operating Ambient
Temperature at 150 lfm airflow

TA

-40

65

°C

Operating Ambient Temperature at
higher (TBD) airflow

TA

-40

75

°C

(See Thermal Considerations section)
Storage Temperature

Tstg

-55

125

°C

Power
Input Power (per Power unit)

Pin

200

W

Power Dissipation (Power unit
Dissipation)

Pdiss

27

TBD

W

Output Power (per Power unit)

Pout

130

TBD

W

Isolation
Input to Output Voltage

1500

Vdc

Advertising