CPS2500D +/-190V Downstream System
5 - 10 Installation
Issue 4 January 2008
Diagnosing Abnormal States
(continued)
Diagnosing
Abnormal States
Abnormal state:
One converter fault and two converter faults.
Step
Action
1
Observe the LEDs.
2
Does the display look like a combination of the states shown in
Figure 5-9: Converter Internal Fault?
3
Yes - Replace the faulty
converter by first removing it as
shown in Figure 5-10 and then
installing a replacement
converter following the
procedure described as QS882A
Converter Installation.
No - Continue to the next step of
Diagnosing Abnormal States.