Diagnosing Abnormal States

(continued)

Diagnosing
Abnormal States

Abnormal state:
One converter fault and two converter faults.

Step

Action

1

Observe the LEDs.

2

Does the display look like a combination of the states shown in
Figure 5-9: Converter Internal Fault?

3

Yes - Replace the faulty
converter by first removing it as
shown in Figure 5-10 and then
installing a replacement
converter following the
procedure described as QS882A
Converter Installation.

No - Continue to the next step of
Diagnosing Abnormal States.

Figure 5-9: Converter Internal Fault

QS882A

A

B

OUT

IN

Green

Green

Green

Green

Red

Red

Green

Red

One Converter

Internal Fault

Two Converters

Internal Faults

QS882A

A

B

OUT

IN

1

1

Figure 5-10: Remove Converter

QS882A

A

B

IN

OUT

1. Press down to

unlatch module

2. Pull forward with

latch depressed