Table 7-A: LED Truth Table

LED Indicators

Condition

Shelf Alarm

A

B

OUT

IN

Green

Green
Green

Green

1

Both circuits receiving input voltage
within acceptable range with input current
below maximum input value, and
delivering acceptable output.

None

A

B

OUT

IN

Green
Green

1

Circuit A receiving input voltage within
acceptable range with input current below
maximum input value and delivering
acceptable output.
Circuit B has never received power.

None

A

B

OUT

IN

1

Neither circuit has received acceptable
input voltage since insertion into powered
shelf.

None

A

B

OUT

IN

Green

Red

Green

1

Input voltage has been interrupted to
circuit B. Occurs after circuit B has been
powered acceptably.

MIN

A

B

OUT

IN

Red

Red

1

Input voltage has been interrupted to both
circuits A and B. Occurs after both
circuits have been powered acceptably.

MAJ

A

B

OUT

IN

Green

Red

Green

Green

1

Circuit B has internal failure but
acceptable input power.
Circuit A has acceptable input and output
power.

MIN

A

B

OUT

IN

Green

Green
Red

Red

1

Both circuit A and circuit B have internal
faults while input power is acceptable.

MAJ

A

B

OUT

IN

Green

Green

1

Load power exceeds source powere
delivery capability. Both circuits in input
limit mode.

MAJ

CPS2500D +/-190V Downstream System

7 - 4 Reference Information

Issue 4 January 2008

Note: Minor and Major alarms are mutually exclusive. Only one can be
asserted at a time.