Spectra and Spectra II Series™ Plug-In and Feeder Busway
Installing and Removing Spectra Busway Plugs

9

the joint cap to the housing spacer of old-style
indoor and the 5/16" x 2" bolt provided on the
new-style indoor and attach to the U clip.

8. When joining Spectra Series Busway to

Spectra II Plug-in Busway, a combination joint
cap will be provided, use the 5/16‖ X 2‖ bolt to
attach this joint cap to the Spectra Series
Busway and the M10 X 16 bolts to attach the
cap to the Spectra II Busway.

Figure 9. Indoor joint cap.

Figure 10. Outdoor joint cap.

Figure 11. Busway joint at the standard distance.

Figure 12. Busway joint at the minimum distance.

Figure 13. Busway joint at the maximum distance.

9. When joining Style II outdoor to new-style

indoor busway, use the existing 3/8" x 1/2" bolt
to attach the joint cap to the housing spacer of
Style II outdoor and the 5/16" x 2" bolt
provided on the new-style indoor and attach
to the U clip.

10. Inspect the busway run for straightness in all

planes and make any adjustments necessary
for good alignment.

11. Grease has been applied to the joint bolt head

and threads to reduce friction. Do not remove
this grease.

12. Tighten the joint bolt with a 5/8‖ or 16-mm

socket wrench until the smaller, top head
breaks off. When the Belleville washers on
both sides are flattened, the bolt is fully
tightened. If the optional Joint-Guard™