Figures 26-29

Table 11 Busway Cross Section

Bar Material

Rated Load
Amps

Dimension “A”
In.

Aluminum

225

3

400

3 3/8

600

4

Copper

225

3

400

3

600

3 3/8

Table 12 Plug Weight (lbs)
QMR Fusible Switches

Amperes

Weight

30

24

60

25

100

28

200

46

400

135

Plug Weight (lbs.) – Circuit Breakers
Frame Type

Weight

E

28

SF

39

Table 13 Weight (lbs./ft.) – Busway

Ampere

Copper

Aluminum

3-wire

4-wire

3-wire

4-wire

225

7

8

5

6

400

7

8

6

7

600

8

9

7

8

800

11

12

9

10

Figure 34. Busway Cross-Section.

Figure 35. End Box.

Installing End Box

Loosen the screw on back of the end box
and separate the end box cap from the end
box.

Slide the end box over the end of the
busway and bolt it to the busway. Note:
make sure the end box is tightly against the
busway.

Place the end box cap on the end box and
bolt it to the busway.

Tighten the screw on the back of the end
box.


Joining Lengths
1. Remove shipping caps from bar end and

discard, but retain the bolts.

2. Remove one joint cap from the two pieces

to be joined, retaining the bolts. Note that
joint pack may be wider than bus.

Figure 31. Edgewise.

Figure 30. Flatwise (Standard).

Figure 32. Trapeze Edgewise.

Figure 33. Trapeze Flatwise.