Spectra and Spectra II Series™ Plug-In and Feeder Busway
Installing and Removing Spectra Busway Plugs

7

Table 3. Dimensions for Spectra RMS™ circuit breaker bus plug.

Frame

Dimensions, in.

Handle

Ht

.

Wt.,

lb.

Outlets Fig.

W

L

D

SED, SEH, SEL, SEP 11.00 13.00 8.00

11.00

25

1

7

SFH, SFL, SFP

11.00 21.25 9.00

12.00

41

1

7

SGH, SGL, SGP

16.75 26.50 12.50 20.50

91

2

8

SKH. SKL, SKP

16.75 36.50 12.50 20.50

160

2

8

Maximum distance from the busway housing to the handle tip.

For ground fault option, increase width by 2.125 inches and length by 6.00

inches.

Table 4. Dimensions for Types QMR and QMW fusible switch bus
plugs, as illustrated in Figure and Figure 8.

Rating,

Volts

Amps

Dimensions, in.

Wt.,

lb

Fig.

W

L

D

Handle

Ht.

Std

Gutter

Ext

Gutter

240 &
600

30

11.25 13.00

18.63

8.75

11.00

24

7

60

11.25 13.00

18.63

8.75

11.00

25

7

100

11.25 18.75

NA

8.75

11.00

28

7

200

16.00 18.75

24.50

8.75

11.00

46

7

400

20.50 18.75

NA

18.75 24.00

135 8

600

20.50 24.50

NA

18.75 28.00

160 8


Table 5. Dimensions for molded-case circuit breaker bus plugs.

Frame

Dimensions, in.

Wt.,

lb

Outlets Fig.

W

L

D

Handle

Height

TEB, TED, THED

11.00 13.00 8.00 11.00

24

1

7

TFJ, TFK, THFK

11.00 18.50 9.50 12.00

44

1

7

TJJ, TJK4, TJK6,
THJK4, THJK6

16.75 24.50 12.50 20.50

95

2

8

TKM8,

THKM8,

THK

16.75 36.50 12.50 20.50

160

2

8

TB1 (fused)

11.00 18.50 8.00 11.00

29

1

7

TB4 (fused)

16.75 30.50 12.50 20.50

65

2

8

TB6 (fused)

16.75 45.25 12.50 20.50

175

2

8

TB8 (fused)

16.75 45.25 12.50 20.50

185

2

8


Table 6. Busway and hanger mounting dimensions, as illustrated in
Figure 2 and Figure 3.

Bars per

Phase

Ampere Rating

Dimensions, in.

Copper

Aluminum

Busway A

Hanger B

1

225–800

225–600

4

3

/

8

10

1

/

4

1000

5

1200

800

5

5

/

8

1350

1000

6

1

/

8

1600

1200

7

2000

1350

8

1

/

2

14

1600

9

1

/

4

2500

10

1

/

4

2000

11

18

1

/

2

2

3000

15

2500

15

1

/

2

4000

3000

18

22

1

/

2

5000

21

1

/

2

26

4000

23







Table 7. Number of busway springs required per busway weight.

Busway

Weight, lb

No. of Springs

Required per Floor

0–600

2

601–1200

4

Over 1200

6


Table 8. Busway weights.

Amperes

Busway Weight, lb/ft

Copper

Aluminum

3 Wire

4 Wire

3 Wire

4 Wire

225

8

9

5

6

400

8

9

5

6

600

8

9

5

6

800

8

9

6

7

1000

10

12

7

8

1200

12

15

8

9

1350

14

17

9

10

1600

16

20

10

12

2000

21

26

12

15

2500

26

33

17

20

3000

32

40

19

23

4000

42

52

25

30

5000

52

66

The door hinges at the left end. The L and W dimensions are shown over
the largest part of the plug.


Figure 7. Bus plugs with door hinges at the left end.




Important Note:

On vertical riser applications use a Minimun of 18‖ of
un-supported flexible conduit connecting to bus plugs.