Spectra and Spectra II Series™ Plug-In and Feeder Busway
Installing Spectra II Series Busway

21



Spectra SeriesTM Busway - Flat wise Outdoor
Elbow Joint


Installation and Maintenance Instructions.

1. Maintain phase alignment using ø side

labels.

2. Align bus within limits shown in the

installations torque joint bolt to 50 Lb-ft (68
N-M)

3. Set shield in place and align outside edges

with edges of elbow side plates and secure
springs.

4. Important: Attach shields to C-Brackets

using 10/32 screws.

5. Attach joint caps:
6. A. Secure joint cap corner with ¼-20 screw

provided

7. B. Torque bolts: 3/8-25 lb-ft
5/16-14-19 Lb-ft
8. Torque ―Set screw‖ to 18-20 inch Lbs then

tighten ―lock nut‖ to joint cap (4) per cap

9. Mega ohm test run before energizing.



































Figure 26. Flat wise outdoor Elbow Joint.



























Figure 27. Flat wise outdoor Elbow Joint asm. Instructions.