GE Industrial Solutions Spectra II Series Plug-in and Feeder Busway with BlueCoat Epoxy Insulation System User Manual

Page 28

Advertising
background image

Spectra and Spectra II Series™ Plug-In and Feeder Busway
Installing Spectra II Series Busway

26

handle position to be up and the OFF handle
position to be down. If plug-assist has been
furnished on the plug, the operating handle
may be used as a wrench to operate the
mechanism.

To install a plug where the rear plug hanger
interferes with a joint cap, it is necessary to
remove the break-off tabs, as shown in the
Figure 40B.

On large plugs, drop rod brackets are
provided for auxiliary support of the plug on
the horizontal runs.

CAUTION: Make certain that the bus plug is level
in all orientations with the busway after all
connections are completed. Failure to level the
plug could result in overheating of the plug
connection.

Installing a Plug Not Equipped with Plug-
Assist
1. Make sure the device is in the OFF position.
2. Loosen the four bolts on the hanger hooks.
3. Align the actuator bar of the bus plug with

the vertical actuator bar slot on the shutter
and push firmly, the shutter will open and
the bus plug stabs fingers will engage the
bus bars.

4. Push the stabs into the full contact with the

busway.

5. Engage the four hanger hooks with the

busway rails and tighten the bolts.

Installing a Plug Equipped with the Plug-Assist
1. Make sure the device is in the OFF position

and the plug-assist indicator is rotated fully
toward the stabs-OUT position.

2. Loosen the four bolts on the hanger hooks.
3. Align the actuator bar of the bus plug with

the vertical actuator bar slot on the shutter
and attach the line end hanger hooks to the
bus rail and tighten.

4. Recheck alignment of actuator and vertical

slot and attach load end hanger hooks to
bus rail and tighten.

5. Engage bus plug by rotating the plug assist

mechanism, the shutter should open and
the bus stabs fingers will engage the bus
bars. The pointer should indicate ―Stabs-IN‖.

NOTE: On the vertically mounted plugs, push up
on the plug to remove the weight of the plug
from the alignment pin before tightening the
bolts in step 4.

WARNING: Be sure that the plug-assist pointer is
lined up with the IN position before turning the
plug on. Failure to do so may result in serious
injury or death.


Removing a Plug
First turn the device OFF. Then follow the
appropriate procedure above in reverse order.

Advertising