Internal wire sizing – GE Industrial Solutions GE ZENITH SERIES MDU User Manual

Page 12

Advertising
background image

Installation Procedures

GE Z

ENITH

C

ONTROLS

MDU Owner’s Manual

601 S

HILOH

R

OAD

January 2013

Plano, TX 75074

Page 12

3.3.

Internal Wire Sizing

Protective

Circuit Breaker

or Actual

Amperage

3,4

Internal Conductors

Phase Wire,

Single

1,3,4,6

Phase Wire,

Two

Parallel

1,3,4,6

Neutral

Wire,

Single

1,3,4,6

Neutral Wire,

Two

Parallel

1,3,4,6

Ground

Wire,

Single

1,3,4,6

25

#10

#14

#10

#12

#10

30

#10

#12

#8

#10

#10

40

#8

#10

#8

#10

#10

50

#8

#10

#6

#10

#10

60

#8

#8

#4

#8

#10

70

#8

#8

#3

#8

#8

80

#6

#8

#3

#8

#8

90

#6

#8

#2

#6

#8

100

#4

#8

#1

#6

#8

110

#4

#8

#1

#4

#6

125

#4

#8

1/0

#4

#6

150

#2

#6

2/0

#3

#6

175

#1

#6

3/0

#2

#6

200

1/0

#4

3/0

#1

#6

225

1/0

#4

4/0

1/0

#4

250

2/0

#3

250MCM

1/0

#4

300

3/0

#2

350MCM

2/0

#4

350

4/0

#1

400MCM

3/0

#3

400

250MCM

1/0

500MCM

4/0

#3

500

350MCM

2/0

750MCM

300MCM

#2

600

500MCM

3/0

1000MCM

400MCM

#1

700

700MCM

4/0

1500MCM

500MCM

1/0

800

800MCM

250MCM

N/A

700MCM

1/0

1000

1000MCM

350MCM

N/A

1000MCM

2/0

Notes:

1. Conductor ratings are based on NEC Table 310.17.
2. Deleted.
3. All wires must be UL listed.
4. Conductors must be separated for air circulation – not bundled
5. Parallel conductor lengths must be equal within 2% (e.g. two parallel conductors 10 feet

long must match in length within 2.4”).

6. For components like circuit breakers, the 75°C column in NEC Table 310.17 must be used.
7. For components like bus bars that allow 90°C connections, the 90°C column in NEC Table

310.17 can be used.