3.0 Installation Procedures

The following section of your owner’s/operator’s manual covers the general requirements for the installation
of your Monitored Distribution Unit and its associated components.

Note: A GE authorized field engineer and/or a licensed electrician must install each unit. Startup by a

GE certified technician is also required to validate the warranty.

3.1.

Equipment placement

The preferred location of your MDU is in the center of the room. Although this location is not
mandatory, it will allow accessibility for preventative maintenance (PM) checks and any other
required services. Follow the National Electrical Code (NEC) and local electrical codes for panel board
clearance requirements. The MDU is intended for indoor installation in an area with ambient
temperatures of 32F to 104F (OC to 40C) with a relative humidity of 0% to 95% (non-condensing).

3.1.1. Clearances

Refer to the MDU shop drawings/submittals for recommended minimum service
clearances. The NEC requires the indicated front and rear clearances for service access
(see Drawings section for typical clearances). Clearance above the unit is required for
cooling airflow (exhaust). Units with optional side cars with the distribution section also
require service access clearance on the side. A MDU produces heat under normal
operation. Figure 1 shows typical MDU weights and heat generation.

Figure 1: MDU Approximate Weights and Heat Generation

MDU

Ratin

g

(kVA)

Output

Heat

(kBTU)

Full Load

Amperage

MDU Weight (Lbs)

208V

Input

480V

Input

600V

Input

Without

Sidecar

w/ (1)

9”-

Sidecar

w/ (2)

9”-

Sidecars

w/ (1)

21”-

Sidecar

w/ (2)

21”-

Sidecars

15

2.7

42

18

14

574

724

874

824

1074

30

4.8

83

36

29

945

1095

1245

1195

1445

50

7.1

139 60

48

1302

1452

1602

1552

1802

75

7.6

208 90

72

1470

1620

1770

1720

1970

100

8.4

278 120 96

1785

1935

2085

2035

2285

125

10.4 347 150 120

1855

2005

2155

2105

2355

150

12.2 416 180 144

1967

2117

2267

2217

2467

200

15.6 555 241 192

2149

2299

2449

2399

2649

225

17.6 625 271 217

2457

2607

2757

2707

2957

300

21.0 833 361 289

3297

3447

3597

3547

3797

400

34.6 N/A 481 384

2900

N/A

N/A

3150

3400

500

43.3 N/A 601 481

3900

N/A

N/A

4150

4400

625

54.1 N/A 752 602

4489

N/A

N/A

4739

4989

750

64.9 N/A 903 721

5390

N/A

N/A

5640

5890

Note: Weights listed are for MDU’s with k-20 transformers and no sidecars. For k-1 weight,

multiply 0.72. For k-13 weights, multiply by 1.12. Weights are for estimate purposes
only. Actual shipping weight may vary.