Page 39

6.0 System Troubleshooting

6.1.

System Safety Precautions

DANGER: There is high voltage equipment inside the MDU cabinet. Always use extreme

caution and follow all recommended safety precautions.

DO NOT operate the MDU without all exterior panels properly in place.

DO NOT allow unauthorized personnel to perform any services on your MDU. Please contact

GE’s field support division at (800) 637-1738 for your authorized service agent and for
assistance.

DO NOT touch any printed circuit board without consulting GE’s field support division.

Improper handling of circuitry could cause damage to your MDU and void the
warranty.

If following the troubleshooting procedures below does not repair your MDU, contact GE’s
Service Team at (800) 637-1738 for scheduling service.

6.1.1. Troubleshooting guidelines (GE Zenith Series Monitoring Package)

S

YMPTOM

P

ROBABLE

C

AUSE

R

EMEDY

No power to unit

Unit not connected to
power J box. Main
Breaker not enabled

Connect unit to Power J box.
Turn on or reset main circuit breaker

Individual output
circuit has no
power.

Output circuit breaker
and or cable is not
connected to MDU.

Connect output circuit to MDU and
energize circuit.

No output from unit
but indicators are
on

Main breaker is
turned off or has
tripped

Check LCD Display for active alarms,
then reset main breaker.

No upstream
communication

Not able to remotely
communicate to the
monitor

Press the ESC key and verify remote
upstream address, baud rate, & parity
are set correctly.

No audible
indication

No audible when an
alarm occurs

Press the ESC key and verify the horn is
enabled.

No able to scroll
thru screens

Cannot see panel
information

Press the enter button firmly to view
MDU information

Not able to see
MDU output
readings

No output voltages or
currents are
displayed

Once on the input screen, use the Up
or down arrows to access output
screens.

Unable to see BCMS
(optional) panels on
front panel

No BCMS currents are
displayed on monitor
screens.

Verify a BCMS is connected to the
downstream port and press the esc
key to setup the number of additional
Panel boards added.