System Monitoring
GE Z
ENITH
C
ONTROLS
MDU Owner’s Manual
601 S
HILOH
R
OAD
January 2013
Plano, TX 75074
Page 25
Feature
Std / Optional
1-V
in
: 1-V
out
, 1-I
out
Std.
1-V
in
: 2-V
out
, 2-I
out
Optional
2-V
in
: 1-V
out
, 1-I
out
Optional
Input Voltage THD
Std.
Input Ground Current
Std.
Neutral Current
Std.
Phase Loss
Std.
Ground Fault Alarm
Std.
Time & Date Stamp for alarms
Std.
Alarm Conditions
Input Frequency (Hz) (Frequency Deviation)
Std.
Input Phase Rotation (Phase Rotation Error)
Std.
Low Transformer Temperature alarm 180 C
Std.
High Transformer Temperature alarm 200 C
Std.
High Temperature Shutdown (may be disabled at customer request)
Std.
True RMS Metering
Std.
Input Voltage - Line to Line (High/Low alarm)
Std.
Output Voltage - Line to Line (High/Low alarm)
Std.
Output Voltage - Line to Neutral (High/Low alarm)
Std.
THD - Input Voltage
Std.
Output Current - A,B & C phases (phase loss and high current alarm)
Std.
Current - Output neutral (High Current Alarm)
Std.
Ground Current (Ground Fault Alarm)
Std.
Over-Voltage / Under-Voltage Shutdown
Optional
Ground Fault Shutdown
Optional
Phase Rotation / Phase Loss Shutdown
Optional