7.0 GE Zenith Series Monitor Alarm Description

A

LARM

N

AME

A

LARM

M

ESSAGE

A

LARM

D

ESCRIPTION

Input Phase Rotation

"PHASE ROTATION"

If the phase rotation is incorrect on the unit's input, the
unit will alarm.

High Temperature Transformer

"THERM OVERTEMP”

If the 180

o

C thermal switches located in the windings of

the transformer reach their rating or better, the unit
will alarm. First part of a two stage high transformer
temperature alarm system.

High Temperature Transformer

Shutdown

"THERM HIGHTEMP"

If the 200

o

C thermal switches located in the windings of

the transformer reach their rating or better, the unit's
main circuit breaker will shunt trip, shutdown the unit.
Second part of a two stage high transformer
temperature alarm system.

Input Voltage Phase A-B High

“INPUT VOLT AB HIGH"

If the input voltage on phase A-phase B goes above the
preset level line to line, the unit will alarm.

Input Voltage Phase B-C High

“INPUT VOLT BC HIGH"

If the input voltage on phase B-phase C goes above the
preset level line to line, the unit will alarm.

Input Voltage Phase C-A High

"INPUT VOLT CA HIGH"

If the input voltage on phase C-phase A goes above the
preset level line to line, the unit will alarm.

Input Voltage Phase A-B Low

“INPUT VOLT AB LOW"

If the input voltage on phase A-phase B goes below the
preset level line to line, the unit will alarm.

Input Voltage Phase B-C Low

“INPUT VOLT BC LOW"

If the input voltage on phase B-phase C goes below the
preset level line to line, the unit will alarm.

Input Voltage Phase C-A Low

"INPUT VOLT CA LOW"

If the input voltage on phase C-phase A goes below the
preset level line to line, the unit will alarm.

Output Voltage Line A-B High

“OUTPUT VOLT AB HIGH"

If the output voltage on line A-line B goes above the
preset level line to line, the unit will alarm.

Output Voltage Line B-C High

" OUTPUT VOLT BC HIGH"

If the output voltage on line B-line C goes above the
preset level line to line, the unit will alarm.

Output Voltage Line C-A High

" OUTPUT VOLT CA HIGH"

If the output voltage on line C-line A goes above the
preset level line to line, the unit will alarm.

Output Voltage Line A-B Low

" OUTPUT VOLT AB LOW"

If the output voltage on line A-line B goes below the
preset level line to line, the unit will alarm.

Output Voltage Line B-C Low

"OUTPUT VOLT BC LOW”

If the output voltage on line B-line C goes below the
preset level line to line, the unit will alarm.

Output Voltage Line C-A Low

"OUTPUT VOLT CA LOW"

If the output voltage on line C-line A goes below the
preset level line to line, the unit will alarm.

Output Voltage Line

A - Neutral High

“OUTPUT VOLT AN HIGH"

If the output voltage on line A-Neutral goes above the
preset level line to Neutral, the unit will alarm.

Output Voltage Line

B - Neutral High

“OUTPUT VOLT BN HIGH"

If the output voltage on line B-Neutral goes above the
preset level line to Neutral, the unit will alarm.

Output Voltage Line

C - Neutral High

“OUTPUT VOLT CN HIGH"

If the output voltage on line C-Neutral goes above the
preset level line to Neutral, the unit will alarm.