Centralized, Centralized 2-5, Figure 2-4: centralized architecture – GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual

Page 23: Architecture, continued

Advertising
background image

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

Issue 10 February 2008

System Description 2 - 5

Architecture, continued

Centralized

Figure 2-4 shows GPS 4848/100 components configured in a
centralized architecture; Figure 2-5 provides a view of the centralized
architecture initial and growth cabinets. Rectifiers, dc distribution
panels, and batteries are cabled to external busbars where a single
system shunt is provided to measure total system current. The initial
cabinet contains ac distribution, rectifiers, the controller, and
termination points for the system interconnect cables. Growth cabinets
contain ac distribution, rectifiers, and cable termination points. A
separate cabinet provides load distribution and protection facilities and
may include load disconnect/reconnect contactors.

This architecture requires extensive up-front planning to determine the
ultimate system capacity and engineering to size the external busbars
appropriately; however, the system plan is not constrained to dedicated
layouts as required for distributed architecture systems.

Figure 2-4: Centralized Architecture

Charge Bus

Charge Return Bus

Discharge Return Bus

Battery Strings

Plant

Shunt

Control

and

Monitor

Loads

Advertising