Low voltage battery disconnect, Control switches, Reference figures, continued – GE Industrial Solutions GPS 4848_100 Users Guide (single rectifier shelf) User Manual

Page 85

Advertising
background image

Galaxy Power System 4848/100 with 595 Series Rectifiers S1:3 and later

Issue 10 February 2008

Troubleshooting Preparations 12 - 7

Reference Figures, continued

Low Voltage

Battery Disconnect

The low voltage battery disconnect (LVBD) feature consists of a
contactor, circuitry on the BJN board, and associated wiring. Control of
the contactor is dictated by the BJN contactor control board and the
controller.

Figure 12-5: Low Voltage Battery Disconnect Contactor

Control Switches

Red Light

Yellow Light

Green Light

CONTACTOR DRIVE BOARD

SW

SW

SW

BOTH SWITCHES DOWN
FORCES CONTACTOR OPEN

CONTACTOR OPEN

CONTACTOR OPEN INITIATED

DOWN FORCES

CONTACTOR CLOSED

REMOTE CONTROL ENABLED

Note: All switches should be in the
up position for normal operation.